- Contact Person : Ms. Zhang Vivian
- Company Name : Hebei Sicon Chat Union Power Equipment Co., Ltd.
- Tel : 86-311-85903759
- Fax : 86-311-85903718
- Address : Hebei,Shijiazhuang,No. 319, Xiangjiang Street, Technology Development Zone
- Country/Region : China
- Zip : 050035
Online High Frequency Modular UPS
SICON-EMI Modular UPS is the new conception modular UPS, features with high efficiency (≥95%), high stability (N+X redundancy) and extremely high cost-efficiency.
System type | CMS-100 | CMS-150 | CMS-200 | CMS-240 | CMS-480 | |
Maximum power | 100KVA | 150KVA | 200KVA | 240KVA | 480KVA | |
Mains input | Input mode | Three-phase four-line+ grounding line/ one phase two-line+ grounding line | ||||
Input voltage | 380V/220V±20%, 400V/230V±20%, 415V/240V±20% | |||||
Input frequency | 50Hz±10%, 60Hz±10% | |||||
Power woke-in (Sec.) | 60secs | |||||
THDI(%) | 3% | |||||
Input power factor | ≥0.99 | |||||
Bypass input | Input voltage | 380V/220V±20%, 400V/230V±20%, 415V/240V±20% | ||||
Input frequency tolerance | 50Hz±10%, 60Hz±10% | |||||
DC input | Rated input voltage | ±384VDC | ||||
input voltage tolerance | 345V~445V DC | |||||
Battery charging | Charging current limited | yes | ||||
Charging time | 10 hours ( 2 hours back up capacity) | |||||
Stability of charging voltage | ±1% | |||||
AC output | UPS power factor | 0.8 | ||||
Output voltage | 380V/220V, 400V/230V, 415V/240V | |||||
Output voltage recovering time | 20ms(load 0~100%) | |||||
Overload capacity | Operate 10 minutes with 125% load | |||||
Transfer from mains to battery supply | 0ms | |||||
Transfer from bypass to inverter supply | 1ms | |||||
Peak factor | 3 : 1 | |||||
Total input harmonics distortion THDI(%) | ≤1%( linear load ) ≤3%( non-linear load ) | |||||
Overall efficiency | ≥95%(AC-AC) |
Online High Frequency Modular UPS